Watlow Series F4 controller

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
input_1_value100I160.1
input_2_value104I160.1
input_3_value108I160.1
set_point_1300I160.1V
set_point_2319I160.1V
power_output_1a103I161%
power_output_1b107I161%
power_output_2a111I161%
power_output_2b115I161%
alarm_1_status102U161
alarm_2_status106U161
input_1_error101U161
input_2_error105U161
input_3_error109U161
cjc1_temp1500I160.1
cjc2_temp1531I160.1
line_frequency1515U161

link settings as documented (unverified): RTU; default 19200 8N1; unit ID 1; Protocol or parity should be 8, n, 1.

⚠ WARNING: Install high- or low temperature-limit control protection in systems where an over temperature fault condition could present a fire hazard or other hazard. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsTouch-safe, removable terminal blocks, accepts 12- to 22-gauge wire
A/B polarityT+/R+, T-/R-
terminationMay need termination and pull-up and pull-down resistors (120 ohm)
isolationSensor input isolation from input to input to output to communication circuitry is 500V~ (ac)
shield/groundShield on EIA/TIA-232 connections
protocol notesTwo sets of Modbus registers contain profile information: edit mode and run mode.
model register0
serial register1
firmware register3
power100-240V~ (ac), -15%, +10%; 50/60Hz, ±5% or 24-28V~ (ac/dc), -15%, +10% (order option), 39VA maximum power consumption
environmentOperating: 32 to 130°F (0 to 55°C), 0 to 90% RH, non-condensing. Storage: -40 to 158°F (-40 to 70°C)
accuracyCalibration accuracy and sensor conformity: ±0.1% of span ±1 LSD @ 77°F ±5°F (25°C ±3°C) ambient
certificationsUL®/C-UL 916-listed, File # E185611, CE to EN 61010, NEMA 4X and IP65, CE EMC to EN 50082-2, CE EMC to EN 55011
doc revision0600-0032-0000 Rev E, October 2000
field reports — community-sourced, unverified (checked 2026-06-11)
  • The Watlow F4 uses a one-register offset for Modbus addressing. To read a value at register address 100, some master systems (such as Red Lion G3 HMIs using Crimson 3.0) must be configured to read address 101. [source]
  • Modbus registers in the 4000 range (typically 4001-4999) used for storing ramp/soak profile data are write-only and cannot be read back via Modbus. [source]
  • The DB-9 connector on TestEquity chambers equipped with the Watlow F4 is wired to accommodate a null-modem cable (pins 2 and 3 swapped), meaning a standard straight-through RS-232 cable cannot be used. [source]
  • confirmed: comms: baud_rates [9600, 19200], default_baud 19200, default_unit_id 1, framing [RTU], parity N, stop_bits 1 — confirmed by Watlow Series F4 User's Manual and TestEquity integration guides
  • confirmed: facts: accuracy ±0.1% of span — confirmed by Watlow Series F4 ramping controller datasheet
  • confirmed: facts: certifications UL®/C-UL 916-listed, File # E185611, CE to EN 61010, NEMA 4X and IP65 — confirmed by Watlow Series F4 ramping controller datasheet
  • confirmed: facts: environment Operating: 32 to 130°F (0 to 55°C), 0 to 90% RH — confirmed by Watlow Series F4 ramping controller datasheet
  • confirmed: facts: identification firmware_register 3, model_register 0, serial_register 1 — confirmed by TestEquity AB48-25d Modbus Temp Ctlr manual
  • confirmed: facts: physical isolation 500VAC — confirmed by Watlow Series F4 ramping controller datasheet
  • confirmed: facts: physical polarity T+/R+, T-/R- — confirmed by Watlow Series F4 User's Manual and wiring diagrams
  • confirmed: facts: physical terminals accepts 12- to 22-gauge wire — confirmed by Watlow Series F4 ramping controller datasheet

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.