verified connector library

Wilo Stratos IF-Module pump

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
set_value_holding1U160.5%
pump_command_holding40U161
operation_mode_holding42U161
bus_command_timer300U161
set_value_input400U160.5%
pump_command_input402U161
operation_mode_input10U161
test_register_700700U161

link settings as documented (unverified): RTU; default 9600 8E1; unit ID 1; Frame formats configurable via Parameter C (Menu 5.2.5.0). Default is 8,E,1 (Code 6).

⚠ When bus command timer state is RESET, writes from Modbus to the Setvalue, Pump command and Operation mode (holding registers 1, 40, 42) have no effect. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsmarked with a (-) and b (+)
A/B polaritya (-) and b (+)
terminationactivated by setting both switches (located close to connection terminals) in the position marked with a non crossed thru resistor symbol
shield/groundShield shall be connected to chassis ground on both ends of the cable as a standard.
wiring notesCharacteristic impedance of the pair shall be 120 Ohm. Wiring shall be done with real shielded twisted pairs.
protocol notesIf input register 700 read fails, try 701 (offset issue).
identification notesSoftware version is on a sticker close to mains terminal at Stratos series and can be read out at 4.4.2.0 for all other pump types.
accuracyThe flow value refers to clean water. Any additives may result in inaccurate or useless values.
doc revision2014-01-03
firmware applicabilityWILO Stratos series >= 5.09, WILO Stratos GIGA (all), WILO BL-E (all), WILO IP-E/DP-E >= 3.00, WILO IL-E/DL-E >= 4.00, WILO Helix EXCEL (all), WILO MVIE/MHIE/HELIX VE (1,1..4 kW) >= 3.00, WILO MVIE/HELIX VE (5,5..7,5 kW) >= 4.00

generated by gemini:gemini-3.5-flash · harvested from https://wilo.cdn.mediamid.com/cdndoc/wilo54872/350003/wilo54872.pdf (Wilo); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.