Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| set_value_holding | 1 | U16 | 0.5 | % |
| pump_command_holding | 40 | U16 | 1 | |
| operation_mode_holding | 42 | U16 | 1 | |
| bus_command_timer | 300 | U16 | 1 | |
| set_value_input | 400 | U16 | 0.5 | % |
| pump_command_input | 402 | U16 | 1 | |
| operation_mode_input | 10 | U16 | 1 | |
| test_register_700 | 700 | U16 | 1 |
⚠ When bus command timer state is RESET, writes from Modbus to the Setvalue, Pump command and Operation mode (holding registers 1, 40, 42) have no effect. — Starkest reads only; we never write a control register.
| terminals | marked with a (-) and b (+) |
| A/B polarity | a (-) and b (+) |
| termination | activated by setting both switches (located close to connection terminals) in the position marked with a non crossed thru resistor symbol |
| shield/ground | Shield shall be connected to chassis ground on both ends of the cable as a standard. |
| wiring notes | Characteristic impedance of the pair shall be 120 Ohm. Wiring shall be done with real shielded twisted pairs. |
| protocol notes | If input register 700 read fails, try 701 (offset issue). |
| identification notes | Software version is on a sticker close to mains terminal at Stratos series and can be read out at 4.4.2.0 for all other pump types. |
| accuracy | The flow value refers to clean water. Any additives may result in inaccurate or useless values. |
| doc revision | 2014-01-03 |
| firmware applicability | WILO Stratos series >= 5.09, WILO Stratos GIGA (all), WILO BL-E (all), WILO IP-E/DP-E >= 3.00, WILO IL-E/DL-E >= 4.00, WILO Helix EXCEL (all), WILO MVIE/MHIE/HELIX VE (1,1..4 kW) >= 3.00, WILO MVIE/HELIX VE (5,5..7,5 kW) >= 4.00 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.