Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| drive_status_1 | 32 | U16 | 1 | |
| fault_contents_1 | 33 | U16 | 1 | |
| data_link_status | 34 | U16 | 1 | |
| frequency_reference | 35 | U16 | 0.01 | Hz |
| output_frequency | 36 | U16 | 0.01 | Hz |
| output_voltage_reference | 37 | U16 | 0.1 | V |
| output_current | 38 | U16 | 0.01 | A |
| output_power | 39 | U16 | 0.1 | kW |
| torque_reference | 40 | I16 | 0.1 | % |
| fault_contents_2 | 41 | U16 | 1 | |
| alarm_contents_1 | 42 | U16 | 1 | |
| input_terminal_status | 43 | U16 | 1 | |
| drive_status_2 | 44 | U16 | 1 | |
| output_terminal_status | 45 | U16 | 1 | |
| frequency_reference_bias | 47 | I16 | 0.1 | % |
| dc_bus_voltage | 49 | U16 | 1 | V |
| torque_monitor | 50 | I16 | 1 | % |
| pid_feedback | 56 | U16 | 0.1 | % |
| pid_input | 57 | I16 | 0.1 | % |
| pid_output | 58 | I16 | 0.1 | % |
| output_frequency_rpm | 62 | U16 | 1 | r/min |
| output_frequency_percent | 63 | U16 | 0.01 | % |
| drive_status | 75 | U16 | 1 | |
| cumulative_operation_time_10h | 152 | U16 | 10 | h |
| cumulative_operation_time_1h | 153 | U16 | 1 | |
| cooling_fan_operation_time_10h | 154 | U16 | 10 | h |
| cooling_fan_operation_time_1h | 155 | U16 | 1 | |
| drive_rated_current | 171 | U16 | 0.01 | A |
| motor_speed | 172 | U16 | 1 |
| terminals | R+, R-, S+, S-, IG |
| termination | Built-in terminating resistance enabled/disabled via DIP switch S2 |
| connector | Removable terminal block |
| max registers/read | 16 |
| response timeout | 2000 ms |
| broadcast | supported |
| model register | 52 |
| power | 200 V Class, Three-Phase Input: 0.1 to 18.5 kW; 200 V Class, Single-Phase Input: 0.1 to 3.7 kW; 400 V Class, Three-Phase Input: 0.2 to 18.5 kW |
| environment | Ambient Temperature: IP20/NEMA Type 1: -10 to +40 °C, IP20/IP00 Open-Chassis: -10 to +50 °C. Humidity: 95% RH or less. Altitude: Up to 1000 m without derating. |
| doc revision | SIEP C710606 16D |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.