Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| pres | 400 | F32BE | 1 | |
| sp | 402 | F32BE | 1 | |
| et | 404 | F32BE | 1 | |
| pres_usl | 412 | F32BE | 1 | kPa |
| pres_lsl | 414 | F32BE | 1 | kPa |
| pres_urv | 416 | F32BE | 1 | kPa |
| pres_lrv | 418 | F32BE | 1 | kPa |
| sp_usl | 420 | F32BE | 1 | MPa |
| sp_lsl | 422 | F32BE | 1 | MPa |
| sp_urv | 424 | F32BE | 1 | MPa |
| sp_lrv | 426 | F32BE | 1 | MPa |
| et_usl | 428 | F32BE | 1 | °C |
| et_lsl | 430 | F32BE | 1 | °C |
| et_urv | 432 | F32BE | 1 | °C |
| et_lrv | 434 | F32BE | 1 | °C |
| pres_damp | 440 | F32BE | 1 | s |
| sp_damp | 446 | F32BE | 1 | s |
| et_damp | 452 | F32BE | 1 | s |
| cap_temp | 1128 | F32BE | 1 | |
| amp_temp | 1130 | F32BE | 1 |
⚠ Do not connect power wiring to the MODBUS(RS-485) terminals. It may damage EJX Multivariable Transmitter. — Starkest reads only; we never write a control register.
| terminals | SUPPLY +, SUPPLY -, MODBUS A, MODBUS B, Ground terminal |
| A/B polarity | MODBUS A, MODBUS B |
| termination | Line termination can be selected by the hardware switch (Bus End / Not Bus End). |
| isolation | The EJX Multivariable Transmitter power supply is not electrically isolated from the RS-485 bus. |
| shield/ground | Grounding is always required for the proper operation of transmitters. |
| response timeout | 3000 ms |
| inter-frame delay | 100 ms |
| broadcast | supported |
| protocol notes | Host timeout period is recommended to be set larger than 3 s when transmitted data size is big. Host communication period between receiving response and sending request is recommended to be set larger than 100 ms under multi-drop connection. |
| model register | 1005 |
| serial register | 1123 |
| firmware register | 1003 |
| FC 43 device ID | supported |
| power | between 9 and 30 V dc with less than 2% ripple, and sufficient current capacity. |
| certifications | ATEX |
| doc revision | IM 01C25R05-01EN 1st Edition |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.